Powercon the two-in-one for voltage and spikes correction.
Large amount of CNC breakdowns are attributed to fluctuations in voltage and various types of electrical noises like spikes, surges, H.F. noises, ground noises, etc.
Electrical noises are generated due to switching action of breakers, heavy, machinery, capacitor switchings, induction hardening, cranes, welding etc. The use of invertors, DC drives, SMPS, further pollutes the electrical environment, causing severe power quality disturbances to various CNC machines, installed in the plant. Advanced CNC machines demand stringent standards of power quality for their smooth and trouble-free operations.
Neel Powercon eliminates major electrical disturbances and provides clean power to your CNC machines.
Features
Technical Specifications
Input Voltage |
340-480 or 300-480 V AC |
Phase |
3 Phase 4 Wire |
Frequency |
47 – 53 H2 |
Output Voltage |
380 or 415 or 200 V AC |
Regulation |
+- 2% Steady State +-5% Dynamic |
Rate Of Correction |
Upto 105 V/sec |
Cooling |
Aircooled |
Ambient |
0-45*C, 90% R.H. |
Common Mode Noise Rejection |
100 db |
Normal Mode Noise Rejection |
40 db |
Duty |
100% Continuous 110% for 60 Sec 200% for 10 sec |
Metering |
Voltage and Currents |
Protection |
Under and Over Voltage Overload and Short Circuit |
Enclosure |
IP 21 |
Ratings |
10,15,20,25,30,40,50,60,75,100,125,150,200,250 KVA |